Sensor Input Data- BAC01 | |||||||||
Item | port | Name | Vlaue of resistance | Description | |||||
1 | TH1 | Toe:outdoor ambient temperature | 10K | temperature range limited and defrost judgement | |||||
2 | TH2 | Tos: total outlet water temperature | 10K | only for the outdoor connection ,it can be used to adjust the load of the unit | |||||
3 | TH3 | Tr:total return water temperature | 10K | only for the outdoor connection ,it can be used to adjust the load of the unit | |||||
4 | TH4 | To: outlet water temperature | 10K | Frost protection | |||||
5 | TH5 | Tcs1:1# suction temperature | 10K | superheat adjustment | |||||
6 | TH6 | Tdis1:1# discharge temperature | 100K | discharge superheat protection | |||||
7 | TH7 | Tevi1:1# EVI inlet temperature | 10K | EVI superheat adjustment | |||||
8 | TH8 | Tevo1:1# EVI outlet temperature | 10K | EVI superheat adjustment | |||||
9 | TH9 | Tcs2: 2# suction temperature | 10K | superheat adjustment | |||||
10 | TH10 | Tdis2:2# discharge temperature | 100K | discharge superheat protection | |||||
11 | TH11 | Tevi2:2# EVI inlet temperature | 10K | EVI superheat adjustment | |||||
12 | TH12 | Tevo2:2# EVIoutlet temperature | 10K | EVI superheat adjustment |
Input / Output Ports Data- BAC01 | |||||||
Item | Port | Description | Remark | ||||
1 | CN1 | RS485 communication port is for slave | when communication with BMS system (Modbus protocol ),if this unit is treated as slave ,the communication port is CN10 to Master | ||||
2 | CN2 | SLM wired controller port | review outdoor unit variables and parameter settings | ||||
3 | CN3 | compressor driver communication port | communication with compressor driver board | ||||
4 | CN5 | Programming port | it is used for upgraded . | ||||
5 | CN6 | EXV 1 port | 1# the master EXV | ||||
6 | CN7 | EXV 2 port | 2# the master EXV | ||||
7 | CN8 | EXV 3 port | 1# EVI | ||||
8 | CN9 | EXV 4 port | 2# EVI | ||||
9 | CN10 | Master communication port | when communication with BMS system (Modbus protocol ),if this unit is treated as master ,the communication port is CN1 to slave. | ||||
10 | CN11 | High/low pressure sensor port | 2# high pressure (Pd2)and low pressure (Ps2)sensor | ||||
11 | Ps1 | low pressure sensor port | 1# low pressure sensor | ||||
12 | Pd1 | high pressure sensor port | 1# high pressure sensor | ||||
13 | CN12 | power input | 220VAC | ||||
14 | CN13 | neutral line | neutral line is for group 1 output | ||||
15 | CN14 | Group1 relays output | O11,O12,O13,O14( 4-way output ) | ||||
16 | CN15 | neutral line | neutral line is for group 2 output | ||||
17 | CN16 | Group2 relays output | O21,O22,O23,O24( 4-way output) | ||||
18 | CN17 | neutral line | neutral line is for group 3 output | ||||
19 | CN18 | Group 3 relays output | O31,O32,O33,O34 (4-way output) | ||||
20 | CN19 | neutral line | neutral line is for group 4 toutput | ||||
21 | CN20 | Group 4 relays output | O41,O42,O43 (3-way output) | ||||
22 | CN21 | Dry contact output | DO1,DO2 (2-way output ,share the same COM) |